Inverter Series-- MD290 AC Drive
■ Approvals
The following table lists the certificates and standards that the product may comply with. For details about the acquired certificates, see the certification marks on the product nameplate.
Certification | Directives | Standard | |
CE | EMC directives | 2014/30/EU | EN 61800-3 |
LVD directives | 2014/35/EU | EN 61800-5-1 | |
RoHS directives | 2011/65/EU | EN 50581 | |
TUV | - | EN 61800-5-1 | |
UL | - | UL508C/UL61800-5-1 | |
C22.2 No.14-13 |
■ Ratings
Table 1-1 Ratings of MD290T18.5G/22P to MD290T75G/90P
Voltage Class | 380 to 480 VAC | ||||||||
MD290TxxG/xxP(B【1】)(-INT) | 18.5G/22P | 22G/30P | 30G/37P | 37G/45P | 45G/55P | 55G/75P | 75G/90P | ||
Dr ive Input | Rated Input Voltage | Three-phase 380 to 480 V, -15% to +10% | |||||||
Rated Input Current, [A] | G type | 49.5 | 59 | 57 | 69 | 89 | 106 | 139 | |
P type | 59 | 65.8 | 71 | 86 | 111 | 143 | 167 | ||
Rated Input Frequency | 50/60 Hz, ±5% | ||||||||
Power Capacity, [kVA] | G type | 45 | 54 | 52 | 63 | 81 | 97 | 127 | |
P type | 54 | 60 | 65 | 79 | 102 | 131 | 153 | ||
Drive Output |
Applicable Motor | G type [kW] | 18.5 | 22 | 30 | 37 | 45 | 55 | 75 |
G type [HP] | 25 | 30 | 40 | 50 | 60 | 75 | 100 | ||
P type [kW] | 22 | 30 | 37 | 45 | 55 | 75 | 90 | ||
P type [HP] | 30 | 40 | 50 | 60 | 75 | 100 | 120 | ||
Output Current, [A] | G type | 37 | 45 | 60 | 75 | 91 | 112 | 150 | |
P type | 45 | 60 | 75 | 91 | 112 | 150 | 176 | ||
Default Carrier Frequency, [kHz] | 6 | 6 | 6 | 5 | 5 | 4 | 3 | ||
Overload Capacity | G type: 150% for 60 Sec, P type: 110% for 60 Sec | ||||||||
Output Voltage | Three phase 0 V to input voltage | ||||||||
Max. Output Frequency | 500 Hz | ||||||||
Braking Resistor | Recommended Power, [kW] | 4 | 4.5 | 6 | 7 | 9 | 11 | 15 | |
Recommended Resistance, Min. [Ω] |
24 |
24 |
19.2 |
14.8 |
12.8 |
9.6 |
6.8 | ||
Therma l Design | Thermal design power, [kW] |
0.478 |
0.551 |
0.694 |
0.815 |
1.01 |
1.21 |
1.57 | |
Air flow, [CFM] |
51.9 |
57.4 |
118.5 |
118.5 |
122.2 |
122.2 |
218.6 | ||
Enclosure | IP20 |
Table 1-2 Ratings of MD290T90G/110P to MD290T160G/200P
Voltage Class | 380 to 480 VAC | |||||
MD290TxxG/xxP(-INT) | 90G/110P | 110G/132P | 132G/160P | 160G/200P | ||
Dr ive Input | Rated Input Voltage | Three-phase 380 to 480 V, -15% to +10% | ||||
Rated Input Current, [A] | G type | 164 | 196 | 240 | 287 | |
P type | 198 | 239 | 295 | 359 | ||
Rated Input Frequency | 50/60 Hz, ±5% | |||||
Power Capacity, [kVA] | G type | 150 | 179 | 220 | 263 | |
P type | 181 | 219 | 270 | 328 | ||
Drive Output |
Applicable Motor | G type [kW] | 90 | 110 | 132 | 160 |
G type [HP] | 120 | 150 | 180 | 220 | ||
P type [kW] | 110 | 132 | 160 | 200 | ||
P type [HP] | 150 | 180 | 220 | 267 | ||
Output Current, [A] | G type | 176 | 210 | 253 | 304 | |
P type | 210 | 253 | 304 | 377 | ||
Default Carrier Frequency, [kHz] | 3 | 3 | 3 | 3 | ||
Overload Capacity | G type: 150% for 60 Sec, P type: 110% for 60 Sec | |||||
Output Voltage | Three phase 0 V to input voltage | |||||
Max. Output Frequency | 500 Hz | |||||
Braking Resistor | Recommended Power, [kW] | 18 | 22 | 26 | 32 | |
Recommended Resistance, Min. [Ω] |
5.3 |
5.3 |
3.5 |
3.5 | ||
Therma l Design |
Thermal design power, [kW] |
1.81 |
2.14 |
2.85 |
3.56 | |
Air flow, [CFM] | 287.2 | 342.2 | 547 | 627 | ||
Enclosure | IP20 |
Table 1-3 Ratings of MD290T200G to MD290T280G and MD290T220P to MD290T315P
Voltage Class | 380 to 480 VAC | ||||||||
Model: MD290Txxxx(-L)**(-INT) | 200G | 220P | 220G | 250P | 250G | 280P | 280G | 315P | |
Dr ive Input | Rated Input Voltage | Three-phase 380 to 480V, -15% to +10% | |||||||
Rated Input Current, [A] | 365 | 410 | 410 | 456 | 441 | 507 | 495 | 559 | |
Power Capacity, [kVA] | 334 | 375 | 375 | 417 | 404 | 464 | 453 | 511 | |
Rated input frequency | 50/60 Hz, ±5% | ||||||||
Drive Output | Applicable Motor, [kW] | 200 | 220 | 220 | 250 | 250 | 280 | 280 | 315 |
Output Current, [A] | 377 | 426 | 426 | 465 | 465 | 520 | 520 | 585 | |
Default carrier frequency, [kHz] | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
Overload Capacity | G type: 150% for 60 Sec P type: 110% for 60 Sec | ||||||||
Output Voltage | Three phase 0 V to input voltage | ||||||||
Max. output frequency | 500 Hz | ||||||||
Braking Resistor | Recommended Power, [kW] | 38 | 38 | 42 | 42 | 48 | 48 | 54 | 54 |
Recommended Resistance, min. [Ω] | 2.9 | 2.9 | 2.7 | 2.7 | 2.3 | 2.3 | 2.1 | 2.1 | |
Thermal Design | Thermal design power, [kW] | 4.15 | 4.55 | 5.06 | 5.33 | 5.69 | 6.31 | 6.91 | 7.54 |
Air flow, [CFM] | 638.4 | 722.5 | 789.4 | 882 | 645 | 860 | 860 | 860 | |
Enclosure | IP00 |
Table 1-4 Ratings of MD290T315G to MD290T450G and MD290T355P to MD290T500P
Voltage Class | 380 to 480 VAC | ||||||||
Model: MD290Txxxx(-L)**(-INT) | 315G | 355P | 355G | 400P | 400G | 450P | 450G | 500P | |
Dr ive Input | Rated Input Voltage | Three-phase 380 to 480V, -15% to +10% | |||||||
Rated Input Current [A] | 565 | 624 | 617 | 708 | 687 | 782 | 782 | 840 | |
Power Capacity, [kVA] | 517 | 571 | 565 | 647 | 629 | 715 | 716 | 768 | |
Rated input frequency | 50/60 Hz, ±5% | ||||||||
Drive Output | Applicable Motor, [kW] | 315 | 355 | 355 | 400 | 400 | 450 | 450 | 500 |
Output Current, [A] | 585 | 650 | 650 | 725 | 725 | 820 | 820 | 880 | |
Default carrier frequency, [kHz] | 3 | 3 | 3 | 3 | 3 | 3 | 3 | 3 | |
Overload Capacity | G type: 150% for 60 Sec (For MD290T450G, the capacity is 130%.) P type: 110% for 60 Sec | ||||||||
Output Voltage | Three phase 0 V to input voltage | ||||||||
Max. output frequency | 500 Hz | ||||||||
Braking Resistor | Recommended Power, [kW] | 54 | 60 | 69 | 69 | 78 | 78 | 87 | 87 |
Recommended Resistance, min. [Ω] | 2.1 | 1.9 | 1.7 | 1.7 | 1.5 | 1.5 | 1.3 | 1.3 | |
Thermal Design | Thermal design power, [kW] | 4.15 | 4.55 | 5.06 | 5.33 | 5.69 | 6.31 | 6.91 | 7.54 |
Air flow, [CFM] | 638.4 | 722.5 | 789.4 | 882 | 645 | 860 | 860 | 860 | |
Enclosure | IP00 |
■ Technical Specifications
Table 2-3 Technical specifications of MD290
Item | Description | |
Standard functions | Input frequency resolution | Digital setting: 0.01 Hz Analog setting: Max. frequency x 0.025% |
Control mode | Voltage/Frequency (V/F) control | |
Torque boost | Customized boost 0.1 % to 30.0 % | |
V/F curve | ● Straight-line V/F curve ● Multi-point V/F curve ● Square V/F curve ● Complete V/F separation ● Half V/F separation | |
Ramp mode | ● Straight-line ramp ● S-curve ramp Four separate acceleration/deceleration time settings in the range of 0s to 6500s. | |
DC injection braking | DC injection braking frequency: 0 Hz to max. frequency DC injection braking active time: 0.0s to 36.0s. Current level of DC injection braking: 0% to 100%. | |
Jog running | Frequency range of jog running: 0.00 to 50.00 Hz Acceleration/Deceleration time of jog running:0.0s to 6500.0s | |
Onboard multiple preset speeds | The system implements up to 16 speeds by using simple PLC function or by using digital input signals. | |
Onboard PID | The system implements the proportionalegral-derivative (PID) function in the closed-loop control. | |
Automatic voltage regulation (AVR) | The system maintains a constant output voltage automatically when the grid voltage changes through the permissible range. | |
Voltage limit and current limit | The system limits the output current and voltage automatically during operation to prevent frequent or excessive trips. | |
Current limit and control | The system limits the current automatically during operation to prevent frequent overcurrent tripping. |
Item | Description | |
Individualized functions | Power dip ride-through | Load feedback energy compensates for any voltage reduction, allowing the drive to continue to operate for a short time during power dips. |
Overcurrent fast prevention | The function helps to avoid frequent overcurrent faults. | |
Virtual I/O | Five groups of virtual digital input/outputs (DI/DO) support simple logic control. | |
Timing control | Time range: 0.0 to 6500.0 minutes | |
Dual-motor switchover | The drive have two groups of motor parameters and can control up to two motors. | |
Multiple field buses | The drive supports four field buses: ● Modbus-RTU ● PROFIBUS-DP ● CANlink ● CANopen | |
Motor overheat protection | Option: The optional input/output (I/O) extension card allows AI3 to receive a signal from the motor temperature sensor input (PT100, PT1000) to implement motor overheat protection. | |
User programmable function | Option: The optional programming card supports secondary development in a programming environment compatible with the Inovance programmable logic controller (PLC). | |
Advanced PC software | Thee software allows users to configure some operating parameters, and provides a virtual oscilloscope display that shows system status. |
Item | Description | |
RUN | Command source | Allows different methods of switching between command sources: ● Operating panel (keypad & display) ● Terminal I/O control ● Serial communication |
Main frequency reference setting channel | Supports up to 10 frequency reference setting channels and allows different methods of switching between frequency reference setting channels: ● Digital setting ● Analog voltage reference ● Analog current reference ● Pulse reference ● Communication reference | |
Auxiliary frequency reference setting channel | Supports up to 10 auxiliary frequency sources, and allows fine tuning of the auxiliary frequency and main & auxiliary calculation. | |
Input terminals | Standard: ● 5 digital input (DI) terminals, one of which supports up to 100 kHz high-speed pulse inputs. ● 2 analog input (AI) terminals, one of which supports only 0 to10 V input, and the other supports 0 to 10 V and 4 to 20 mA current input. Expanded capacity: ● 5 digital input (DI) terminals. ● 1 AI terminal that supports –10 to 10 V voltage input and PT100/PT1000 motor temperature sensor inputs. | |
Output terminals | Standard ● 1 high-speed pulse output terminal (open-collector) for a square-wave signal output in the frequency range 0 to 100 kHz ● 1 digital output (DO) terminal ● 1 relay output terminal ● 1 analog output (AO) terminal that supports either a current output in the range 0 to 20 mA or a voltage output in the range 0 to 10 V. Expanded capacity: ● 1 extra DO terminal ● 1 extra relay output terminal ● 1 extra AO terminal that supports either a current output in the range 0 to 20 mA or a voltage output in the range 0 to 10 V. |
■ De-rating
The drive can be operated at above rated ambient temperature, altitude and default carrier frequency by de-rating drive capacity.
Carrier Frequency De-rating
When carrier frequency of the drive is increased above default setting, you need to de-rate rated drive output current according to the following table:
Power | Carrier Frequency | |||||
Phd (kW) | 3 kHz | 4 kHz | 5 kHz | 6 kHz | 7 kHz | 8 kHz |
18.5 | 100.0% | 100.0% | 100.0% | 100.0% | 95.7% | 91.6% |
22 | 100.0% | 100.0% | 100.0% | 100.0% | 95.5% | 91.4% |
30 | 100.0% | 100.0% | 100.0% | 100.0% | 93.5% | 87.7% |
37 | 100.0% | 100.0% | 100.0% | 94.4% | 89.0% | 84.0% |
45 | 100.0% | 100.0% | 100.0% | 94.0% | 88.6% | 83.7% |
55 | 100.0% | 100.0% | 94.1% | 88.9% | 84.0% | 79.5% |
75 | 100.0% | 91.8% | 84.2% | 77.5% | - | - |
90 | 100.0% | 90.8% | 82.3% | 74.9% | - | - |
110 | 100.0% | 91.9% | 84.4% | 77.7% | - | - |
132 | 100.0% | 93.1% | 86.7% | 80.8% | - | - |
160 | 100.0% | 92.6% | 85.7% | 79.7% | - | - |
200 | 100.0% | 90.0% | 81.0% | 73.1% | - | - |
220 | 100.0% | 90.8% | 82.5% | 75.1% | - | - |
250 | 100.0% | 91.2% | 83.2% | 76.2% | - | - |
280 | 100.0% | 91.8% | 84.3% | 77.8% | - | - |
315 | 100.0% | 91.7% | 83.9% | 77.0% | - | - |
355 | 100.0% | 92.3% | 85.2% | 78.7% | - | - |
400 | 100.0% | 91.4% | 83.6% | 76.8% | - | - |
- Ambient Temperature De-rating
Drive operation between -10°C to 40°C is normal without de-rating. Operation between 40°C and 50°C requires output current de-rating. Rated output current must be de-rated for 1.5% per 1°C temperature rise. Permissible maximum temperature is 50°C.
(3) Altitude De-rating
The drive must be de-rated for an installation altitude of above 1000 meters because cooling effect available from ambient air reduces. Rated output current must bede-rated for 1% per 100 meters. Maximum altitude is 3000 meters.